PUMPS CIRCULATION FOR FOUNTAINS APPLICATION

PUMPS CIRCULATION FOR FOUNTAINS

This is an application which consists of 3 pumps circulate per 2 a 4th filter pump and a 5th waste water pump for controlling a fountain. The application was developed with Zelio Logic SR2B201FU with real time Clock and Display capabilities.

The requirements are

1) 3 Pumps working per 2 in circular rotation (1-2) , (2-3), (3-1) for scheduled time during the day

2) 1 Filter Pump which running schedule

3) 1 waste water Pump which run with a level sensor command

4) 1 electrovalve which open with a filling level sensor

5) 1 low level sensor protecting the 4 pumps for dry working

6) 1 Voltage detector

Schedule program for the 3 pumps with 1 zelio button is:

1st program : (08:00 – 14:00) and (17:00 - 24:00)

2nd program : (07:00 – 15:00) and (17:00 – 01:00)

3rd program : (07:00 – 16:000 and (17:00 – 01:00)

4th program : (07:00 – 01:00)

Schedule for 4th filter pump is 2 hours stop/ 1 hour run per day

INPUTS

I1 waste water level sensor  - NO

I2 Voltage Detector and Emergency Stop - NC

I3 Dry (Low Level) sensor – Deenergise Pumps – except waste water pump  - NC

I4 Filling level sensor (Valve activation) - NC

I5 Thermal relay Pump No1 - NC

I6 Thermal relay Pump No2 - NC

I7 Thermal relay Pump No3 - NC

I8 Thermal relay filter pump - NC

I9 Thermal relay waste water pump - NC

I10 Reset Button - NO

Z1 Zelio Start and Select Schedule program button . Position 1 Stop. Other positions 2 to 5 schedule program running.

NC : Normally close contact  - NO : Normally Open contact (external)
OUTPUTS

O1 RUN Pump No1

O2 RUN Pump No2

O3 RUN Pump No3

O4 RUN Filter Pump

O5 RUN Waste water Pump

O6 Filling Valve command OPEN

O7 Alarm Horn

Note: The program needs a latch at the Z1 cam encoder in order to restart after a power failure. It is left upon the user to decide if this requirement will  be added . In this application the customer have chosen NOT to have that capability. A manual restart needed . Alarm with horn when power voltage fail
You could request for the program